KINGELEK Product:
|
|
|
|
|
|
|
|
For NT and NH fuse links
¦ According to EN60947-1 and EN60947-3
¦ Rated voltage:690V AC/440V DC
¦ Rated currents:160A,250A,400A/630A
¦ Rated insulation voltage:size NH00 to NH3 AC 750V
¦ Rated short-circuit current:50kA AC eff,25kA DC eff
¦ Degree of protection IP 20 with operational status,Ip 10 with open slewing equipment. |
|
|
Switch Current A |
160 |
250 |
400 |
630 |
Rated isulation voltage V |
8000 |
Rated Current A |
380V
AC20 |
160 |
250 |
400 |
630 |
380V
AC21 |
160 |
250 |
400 |
630 |
380V
AC22 |
160 |
250 |
400 |
630 |
660V
AC20 |
160 |
250 |
400 |
630 |
660V
AC21 |
100 |
200 |
315 |
425 |
660V
AC22 |
100 |
160 |
315 |
315 |
Fuse type |
NT00 |
NT1 |
NT2 |
NT3 |
Fuse link |
380V
fuse current A
(breaking capacity)
|
20 A25 A32 A35
40 A50 A63 A80
100 A125 A160
( =100kA)
|
80 A100 A125
160 A200
224 A250
( =100kA) |
125A160A200
224A250A300
315A355A400
( =100kA)
|
315A355A400
425A500A630
( =100kA) |
660V
fuse currentA
(breaking capacity |
20 A25 A32 A35
40 A50 A63 A80
100
( =50kA)
|
80 A100 A125
160 A200
( =50kA) |
123A160A200
224A250A300
315
( =50kA) |
315A355
400A425
( =50kA)
|
|
|
|
|
|
|
|
|
|
|
|
|
Switch current (A) |
Rated voltage (V) |
Rated current (A) |
Fuse type |
Fuse rated current(A) |
160 |
400 |
160 |
NT00 |
4,6,10,16,20,25,32
36,40,50,63,80,100
125,160
|
690 |
100 |
4,6,10,16,20,25,32
36,40,50,63,80,100
|
250 |
400 |
250 |
NT1 |
80,100,125,160,
200,225,250 |
690 |
200 |
80,100,125,160,200 |
400 |
400 |
400 |
NT2 |
125,160,200,225,250
300.315,355,400 |
690 |
315 |
125,160,200,225,250
300,315 |
630 |
400 |
630 |
NT3 |
315,355,400
425,500,630 |
690 |
425 |
315,355,400,425 |
|
|
|